Switchgear: The apparatus used for switching, controlling and
protecting the electrical circuits and equipment is known as
switchgear.
Classification of Switchgear:
Switchgear can be classified on the basis of voltage level
into the following:
1. Low voltage (LV) Switchgear: up to 1KV
2. Medium voltage (MV) Switchgear: 3 KV to 33 KV
3. High voltage (HV) Switchgear: Above 33 KV.
Components of LT Switchgear:
The term LT Switchgear includes low voltage Circuit Breakers,
Switches, off load electrical isolators, HRC fuses, Earth Leakage
Circuit Breaker, Miniature Circuit Breakers (MCB) and Molded
Case Circuit Breakers (MCCB) etc i.e. all the accessories
required to protect the LV system.
The most common use of LV switchgear is in LV distribution
board.
FUSE:
Fuse is the simplest and cheapest device used for
interrupting an electrical circuit under short circuit, or
excessive overload, current magnitudes.
The action of a fuse is based upon the heating effect of the
electric circuit.
The fuse has inverse time-current characteristics.
The part which actually
melts and opens the circuit
is known as the fuse
element.
Fuses have following
advantages and
disadvantages:
Advantages:
1. It is cheapest form of protection available.
2. It needs no maintenance.
3. Its operation is inherently completely automatic unlike a
circuit breaker which requires an elaborate equipment for
automatic action.
4. It interrupts enormous short circuit currents without noise,
flame, gas or smoke.
Disadvantages:
1. Considerable time is lost in rewiring or replacing a fuse after
operation.
2. On heavy short circuits, discrimination between fuses in
series cannot be obtained unless there is considerable
differences in the relative sizes of the fuse concerned.
3. The current-time characteristics of a fuse cannot always be
correlated with that of the protected device.
Fuse is provided only in phase or live pole, never on
neutral pole.
FUSE UNITS:
The various types of fuse units, most commonly available are:
1. Round type fuse unit.
2. Kit-Kat type fuse unit.
3. Cartridge type fuse unit.
4. HRC (High Rupturing Capacity) fuse units.
5. Semiconductor fuse units.
Switch Fuse Unit (SFU): Switch fuse is a combined unit and is
known as an iron clad switch, being made of iron. It may be
double pole for controlling single phase two-wire circuits or
triple pole for controlling three-phase, 3-wire circuits or triple
pole with neutral link for controlling 3-phase, 4-wire circuits.
The respective switches are known as double pole iron clad
(DPIC), triple pole iron clad (TPIC), and triple pole with neutral
link iron clad (TPNIC) switches.
MCB: An MCB is an automatically operated electrical switch. Miniature circuit breakers are intended to prevent damage to an electrical circuit as a result of excess current. They are designed to trip during an overload or short circuit to protect against electrical faults and equipment failure.
MCBs are widely used as isolating components in domestic, commercial, and industrial settings. They form part of a broader family of more powerful circuit-breaking components.
Working:
Excess current causes the bimetallic strip within the MCB to heat, bend, and trip. This releases a switch that moves the electrical contact points apart to confine the arc (electrical discharge). The arc is divided and cooled by an insulated metal strip called the arc chute. The contacts close again once the fault has been fixed and the MCBs are reset.
An MCB is designed to protect against both overloading and short-circuiting. These are detected differently using separate processes. Overload protection is provided by the bimetallic strip using thermal operation, whereas short-circuit protection is provided by the tripping coil via electro-magnetic operation.
If the discharge is especially high, the MCB will trip (activate) very quickly – within one-tenth of a second. When the overcurrent is closer to the safety limits, the component will be slower to respond.
Earth Leakage Circuit Breaker (ELCB): It is a device that
provides protection against earth leakage. These are of two
types.
1. Current operated earth leakage circuit breaker:
It is used
when the product of the operating current in amperes and the
earth-loop impedance in ohms does not exceed 40. such circuit
breakers is used where consumer’s earthing terminal is
connected to a suitable earth electrode. A current-operated earth leakage circuit breaker is applied to a
3-phase, 3-wire circuit.
In normal condition when there is no earth leakage, the
algebraic sum of the currents in the three coils of the current
transformers is zero, and no current flows through the trip coil.
In case of any earth leakage, the currents are unbalanced and
the trip coil is energized and thus the circuit breaker is tripped.2. Voltage operated earth leakage circuit breaker: It is suitable
for use when the earth –loop impedance exceeds the values
applicable to fuses or excess-current circuit breaker or to current
operated earth leakage circuit breaker. When the voltage between
the earth continuity conductor (ECC) and earth electrode rises to
sufficient value, the trip coil will carry the required current to trip
the circuit breaker. With such a circuit breaker the earthing lead
between the trip coil and the earth electrode must be insulated; in
addition, the earth electrode must be placed outside the
resistance area of any other parallel earths which may exist. The
tripping operation may be tested by
means of a finger-operated test button
which passes a predetermined current
from the line wire through a high
resistance to trip the coil and thus to
earth. This test operation should be
performed regularly.

Molded Case Circuit Breaker (MCCB) :
It is a type of electrical protection device that can be used for a wide range
of voltages, and frequencies of both 50 Hz and 60 Hz, the main
distinctions between molded case and miniature circuit breaker are that
MCCB can have current rating up to 2500 amperes, and its trip setting are
normally adjustable. MCCBs are much larger than MCBs.
An MCCB has
three main functions:
• Protection against overload.
• Protection against electrical faults.
• Switching a circuit ON and OFF. This is a less common function of
circuit breakers, but they can be used for that purpose if there is not an
adequate manual switch.
Operating Mechanism:
• Overload protection is accomplished by means of a thermal
mechanism. MCCBs have a bimetallic contact which expands
and contracts in response to changes in temperature. Under
normal operating conditions, the contact allows electric
current through the MCCB. However, as soon as the current
exceeds the adjusted trip value, the contact will start to heat
and expand until the circuit is interrupted. The thermal
protection against overload is designed with a time delay to
allow short duration overcurrent, which is a normal part of
operation for many devices. However any over current
conditions, that lasts more than what is normally expected
represent an overload, and the MCCB is tripped to protect the
equipment and personnel.
• On the other hand, fault protection is accomplished with
electromagnetic induction, and the response is instant. Fault
currents should be interrupted immediately, no matter if their
duration is short or long. Whenever a fault occurs, the
extremely high current induces a magnetic field in a solenoid
coil located inside the breaker-this magnetic induction trips a
contact and current is interrupted. As a complement to the
magnetic protection mechanism, MCCBs have internal arc
dissipation measures to facilitate interruption.
Comments
Post a Comment